Manual door air shower control panel button instructions:
1Emergency stop buttonWhenever the emergency stop button is pressed, the red emergency stop indicator light will turn on and automatically disconnect all outputs except for the lighting. When pressed again, the system will return to its initial state. This button is mainly used when the inner and outer doors cannot be unlocked, the air shower cannot be automatically closed, and other maintenance is required.
2Wind shower buttonAfter the inner and outer doors are closed, press the manual button to enter the air shower process. This button is mainly used for door magnets, infrared malfunctions, or fan maintenance and repair
3Lighting buttonThe 'Lighting' button can be used to turn on and off the indoor lighting of the air shower. This button is mainly used when the door magnet fails or when the lighting fixture is under maintenance.
4Up and down buttonsBefore or after the start or end of the air shower, adjust the delay time of the air shower by pressing the up and down buttons; Adjust or select options when entering internal parameter settings.
Conventional air shower workflow:
1. Enter the clean area:
When personnel entering the clean area open the outer door, the electric lock of the inner door automatically locks to prevent the flow of unpurified air into the clean area, and the lighting of the air shower room lights up.
1.2 After entering the air shower room and closing the outer door, the voice prompt reads: "Hello, please stand in the sensing area." The system's infrared probe begins to detect whether there is anyone. If someone is detected, the system will immediately enter the air shower process.
1.3 Before the air shower, lock the inner and outer doors, start the air shower by starting the fan, and at the same time, start the countdown for the air shower. Voice prompt: 'Working, please rotate your body 360 degrees'.
If the system does not detect anyone in the air shower room within the specified time after the outer door is closed, it will return to standby mode.
During the 1.5 air shower process, if someone presses the up, down, or lighting switch, the voice will prompt: 'Working, please do not touch the switch casually'.
During the air shower process, if someone presses the emergency stop switch, the air shower will end. Press the emergency stop button again to cancel the emergency stop status.
After the 1.7 air shower is completed, the inner door will unlock and the voice prompt will say: 'The air shower is finished, please exit through the rear door'.
After personnel exit the air shower room and close the inner door, the system returns to its initial state and waits for the next use.
1.9 After the air shower is completed and the inner door is unlocked. The personnel inside did not leave the air shower room within the specified time, and the system defaults that the person may have left and automatically returns to standby mode.
After the lighting is turned on, if it is not triggered again within the specified time, it will automatically turn off.
2. Leaving the clean area:
2.1 Open the inner door, lock the electric lock of the outer door, and turn on the air shower lighting;
2.2 People enter the air shower room, close the inner door, and the system begins to check if anyone is in the air shower room. If no one is detected within the specified time, the inner and outer doors will be unlocked;
2.3 If someone is detected, the system will lock the inner door when the personnel open the outer door. When the outer door is closed, the system will return to its initial state;
2.4 In case of special circumstances, personnel can choose to return to the clean area. The system will wait for personnel to open the inner door, and the outer door will be electrically locked. When the inner door is closed, the system will return to its initial state;
After the outer door is opened, if no one is detected within the specified time, if the outer door is opened first, the system will enter the clean area process; If the inner door is opened first at this time, the system will enter the process of leaving the clean area
2.6 After the lighting is turned on, if there is no lighting within the set time